Swegon Golden Gate 2008

Detaljer

Typ
Drivrutin
Upplaggd av
Ove Jansson, Abelko Innovation
Version
1
Uppdaterad
2013-08-28
Skapad
2013-08-28
Kategori
Modbus, Ventilation
Visningar
3673

Beskrivning

Drivrutin

Bruksanvisning

Hur man installerar typdefinitionerna och driftsätter modulerna finns beskrivet i användarmanualen, kapitel 18.7.

Juridisk information

Alla skript tillhandahålls i befintligt skick och all användning sker på eget ansvar. Felaktig använding kan leda till skadad eller förstörd utrustning.

Skript kod

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLDEN GATE read input registers 1-20        
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGAnalog1 NAMED "Swegon GG AI1" TYPEID 21213 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
                                       %                                   Ver A(4)       Ver B
    R1  : "Operation mode"  [" "];     %Ver A: AHU handterminal menu       1-200
                                       %Ver B: Operationstatus for the AHU                00 = Stop alarm
                                       %                                                  01 = Manual stop
                                       %                                                  02 = Ext.stop
                                       %                                                  03 = RS232 stop
                                       %                                                  04 = S-CL stop
                                       %                                                  10 = Manual LS
                                       %                                                  11 = S-CL LS
                                       %                                                  12 = Ext.LS
                                       %                                                  13 = RS232 LS
                                       %                                                  14 = Prolonged LS
                                       %                                                  20 = Manual HS
                                       %                                                  21 = Ext.HS
                                       %                                                  22 = RS232 HS
                                       %                                                  23 = S-CL HS
                                       %                                                  24 = Prolonged HS
                                       %                                                  30 = SN-Cool
                                       %                                                  31 = Reecooling
                                       %                                                  40 = Manual test OP
                                       %                                                  41 = Duct airflow adj
                                       %                                                  42 = Filtercalibration
                                       %
                                       %                                   Ver A(4)       Ver B
    R2  : "Delay HS_min"    ["m"];     %Remaining time highspeed           0-59           0-59           
    R3  : "Delay HS_hour"   ["h"];     %Remaining time highspeed           0-23           0-23           
    R4  : "Delay LS_min"    ["m"];     %Remaining time lowspeed            Not used       0-59           
    R5  : "Delay LS_hour"   ["h"];     %Remaining time lowspeed            Not used       0-23           
    R6  : "SF flow"         ["l/s"];   %Supply air fan flow                0-4000l/s      0-8000l/s      
    R7  : "EF flow"         ["l/s"];   %Exhaust air fan flow               0-4000l/s      0-8000l/s      
    R8  : "SF VAV level"    ["%"];     %SA input signal VAV/Forcing func   0-100.0%       0-100.0%       
    R9  : "EF VAV level"    ["%"];     %EA input signal VAV/Forcing func   0-100.0%       0-100.0%       
    R10 : "SF level"        ["%"];     %Running level supply air fan       0-100.0%       0-100.0%       
    R11 : "EF level"        ["%"];     %Running level exhaust air fan      0-100.0%       0-100.0%       
    R12 : "Heat exch.lev."  ["%"];     %Running level heat exchanger       0-100.0%       0-100.0%       
    R13 : "SA temp"         ["°C"];    %Supply air temp                    0-40.00°C      -55.00-125.00°C
    R14 : "OUT-D temp"      ["°C"];    %Outdoor air temp                   -20.00-40.00°C -55.00-125.00°C
    R15 : "EA temp"         ["°C"];    %Exhaust air temp                   0-40.00°C      -55.00-125.00°C
    R16 : "SA temp setp"    ["°C"];    %Supply air regulator temp setpoint 0-40.00°C      -55.00-125.00°C
    R17 : "FP temp"         ["°C"];    %Frost protection temp              0-40.00°C      -55.00-125.00°C
    R18 : "Reheat level"    ["%"];     %Level for reheater coi             0-100.0%       0-100.0%       
    R19 : "Cooling level"   ["%"];     %Level for cooling                  0-100.0%       0-100.0%       
    R20 : "SA filt level"   ["%(Pa)"]; %Level for supply air filter        0-100.0%       0-2000Pa       

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput1 NAMED "Register 1-20" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(0);      % Start address register
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(R1  := DATA;);     
      DATA[5]  -> RWORD(R2  := DATA;);     
      DATA[7]  -> RWORD(R3  := DATA;);     
      DATA[9]  -> RWORD(R4  := DATA;);     
      DATA[11] -> RWORD(R5  := DATA;);     
      DATA[13] -> RWORD(R6  := DATA;);           % 0-4000l/s       0-8000l/s      
      DATA[15] -> RWORD(R7  := DATA;);           % 0-4000l/s       0-8000l/s      
      DATA[17] -> RWORD(R8  := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[19] -> RWORD(R9  := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[21] -> RWORD(R10 := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[23] -> RWORD(R11 := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[25] -> RWORD(R12 := DATA / 10;);      % 0-100.0%        0-100.0%
           
                                                 % 0-40.00°C       -55.00-125.00°C
      DATA[27] -> RWORD(IF DATA > 32767 THEN R13 := 0 - (1 + (65535-DATA)) / 100;    % Negativ ?
                        ELSE                 R13 := DATA /100;
                        ENDIF;
                       );
                                                 %-20.00-40.00°C  -55.00-125.00°C
      DATA[29] -> RWORD(IF DATA > 32767 THEN R14 := 0 - (1 + (65535-DATA)) / 100;    % Negativ ?
                        ELSE                 R14 := DATA /100;
                        ENDIF;
                       );
                                                 % 0-40.00°C       -55.00-125.00°C
      DATA[31] -> RWORD(IF DATA > 32767 THEN R15 := 0 - (1 + (65535-DATA)) / 100;    % Negativ ?
                        ELSE                 R15 := DATA /100;
                        ENDIF;
                       );
                                                 % 0-40.00°C       -55.00-125.00°C
      DATA[33] -> RWORD(IF DATA > 32767 THEN R16 := 0 - (1 + (65535-DATA)) / 100;    % Negativ ?
                        ELSE                 R16 := DATA /100;
                        ENDIF;
                       );
                                                 % 0-40.00°C       -55.00-125.00°C
      DATA[35] -> RWORD(IF DATA > 32767 THEN R17 := 0 - (1 + (65535-DATA)) / 100;    % Negativ ?
                        ELSE                 R17 := DATA /100;
                        ENDIF;
                       );

      DATA[37] -> RWORD(R18 := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[39] -> RWORD(R19 := DATA / 10;);      % 0-100.0%        0-100.0%       
      DATA[41] -> RWORD(R20 := DATA / 10;);      % 0-100.0%        0-2000Pa       

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLD GATE read input registers 21-38
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGAnalog2 NAMED "Swegon GG AI2" TYPEID 21214 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
                                        %                                    Ver A(4)       Ver B
    R21 : "EA filt level"    ["%(Pa)"]; %Level for exhaust air filter        0-100.0%       0-2000Pa
    R22 : "SF filt alarm"    ["Pa"];    %Alarm level for supply air filter   Not used       0-2000Pa
    R23 : "EF filt alarm"    ["Pa"];    %Alarm level for exhaust air filter  Not used       0-2000Pa
    R24 : "Active alarm"     [" "];     %Active alarm No                     0-48           0-49    
    R25 : "Unit version"     [" "];     %0=No communication                  0-1            0,2     
                                        %1=Version 4 or A
                                        %2=Version B
    R26 : "Input sts 1-16 "  [" "];
    R27 : "Input sts 17-32"  [" "];
    R28 : "Input sts 33-48"  [" "];
    R29 : "Input sts 49-64"  [" "];
    R30 : "Input sts 65-77"  [" "];
    R31 : "SF flow setp"     ["l/s"];   %Setpoint supply fan flow            0-4000l/s      0-8000l/s
    R32 : "EF flow setp"     ["l/s"];   %Setpoint exhaust fan flow           0-4000l/s      0-8000l/s
    R33 : "EA temp setp"     ["°C"];    %Setpoint exhaust air temperature    0-40.00°C      0-40.00°C
    R34 : "SF VAV level"     ["%"];     %Level supply fan VAV regulator      Not used       0-100.0% 
    R35 : "EF VAV level"     ["%"];     %Level exhaust fan VAV regulator     Not used       0-100.0% 
    R36 : "Operating time"   ["days"];  %Operating days                      0-9999         0-9999   
    R37 : "Program version"  [" "];     %Program version in GOLD AHU         Not used       0-65535  
    R38 : "Coolforcing lev"  ["%"];     %Coolforcing level                   0-100.0%       0-100.0% 

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput2 NAMED "Register 21-38" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(20);     % Start address register
      DATA[4]  := RWORD(18);     % Number of registers

    ANSWER SIZE 41
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(36);      % Byte count
      DATA[3]  -> RWORD(R21 := DATA / 10;);            % 0-100.0%       0-2000Pa
      DATA[5]  -> RWORD(R22 := DATA;);                 % Not used       0-2000Pa
      DATA[7]  -> RWORD(R23 := DATA;);                 % Not used       0-2000Pa
      DATA[9]  -> RWORD(R24 := DATA;);                 % 0-48           0-49    
      DATA[11] -> RWORD(R25 := DATA;);                 % 0-1            0,2     
      DATA[13] -> RWORD(R26 := DATA;);                 % 
      DATA[15] -> RWORD(R27 := DATA;);                 % 
      DATA[17] -> RWORD(R28 := DATA;);                 % 
      DATA[19] -> RWORD(R29 := DATA;);                 % 
      DATA[21] -> RWORD(R30 := DATA;);                 % 
      DATA[23] -> RWORD(R31 := DATA;);                 % 0-4000l/s      0-8000l/s   
      DATA[25] -> RWORD(R32 := DATA;);                 % 0-4000l/s      0-8000l/s
      DATA[27] -> RWORD(R33 := DATA /100;);            % 0-40.00°C      0-40.00°C
      DATA[29] -> RWORD(R34 := DATA / 10;);            % Not used       0-100.0% 
      DATA[31] -> RWORD(R35 := DATA / 10;);            % Not used       0-100.0% 
      DATA[33] -> RWORD(R36 := DATA;);                 % 0-9999         0-9999   
      DATA[35] -> RWORD(R37 := DATA;);                 % Not used       0-65535  
      DATA[37] -> RWORD(R38 := DATA / 10;);            % 0-100.0%       0-100.0% 

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLDEN GATE read digital inputs 1-20
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading digital inputs
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGDigital1 NAMED "Swegon GG DI1" TYPEID 21215 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
    DI1  : "Cool energy rec";  %Cool energy recovery function           
    DI2  : "S.Night cooling";  %Summer night cooling                    
    DI3  : "Group alarm A";    %Alarm relay output-A                    
    DI4  : "Group alarm B";    %Alarm relay output-B                    
    DI5  : "Highspeed";        %Operating cases.                        
    DI6  : "Lowspeed";         %Operating cases.                        
    DI7  : "Stop";             %Operating cases.                        
    DI8  : "Heating relay";    %Heating function is active.             
    DI9  : "Cooling relay 1";  %Cooling function stage 1 is active.     
    DI10 : "Cooling relay 2";  %Cooling function stage 2 is active.     
    DI11 : "Cooling cpr 1";    %Compressor 1, in Cooler is active.      
    DI12 : "Cooling cpr 2";    %Compressor 2, in Cooler is active.      
    DI13 : "Reserve 1";        %Not used in this version.               
    DI14 : "Reserve 2";        %Not used in this version.               
    DI15 : "Digital In 1";     %Input 1, on Ethernet module is active.  
    DI16 : "Digital In 2";     %Input 2, on Ethernet module is active.  
    DI17 : "Alarm no. 1";      %
    DI18 : "Alarm no. 2";      %
    DI19 : "Alarm no. 3";      %
    DI20 : "Alarm no. 4";      %

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalInput1 NAMED "DI 1-20" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(0);      % Start adress
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI1 := 1; ELSE DI1 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI2 := 1; ELSE DI2 := 0; ENDIF;
                       IF (DATA & 4)   THEN DI3 := 1; ELSE DI3 := 0; ENDIF;
                       IF (DATA & 8)   THEN DI4 := 1; ELSE DI4 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI5 := 1; ELSE DI5 := 0; ENDIF;
                       IF (DATA & 32)  THEN DI6 := 1; ELSE DI6 := 0; ENDIF;
                       IF (DATA & 64)  THEN DI7 := 1; ELSE DI7 := 0; ENDIF;
                       IF (DATA & 128) THEN DI8 := 1; ELSE DI8 := 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI9 := 1; ELSE DI9 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI10:= 1; ELSE DI10:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI11:= 1; ELSE DI11:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI12:= 1; ELSE DI12:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI13:= 1; ELSE DI13:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI14:= 1; ELSE DI14:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI15:= 1; ELSE DI15:= 0; ENDIF;
                       IF (DATA & 128) THEN DI16:= 1; ELSE DI16:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(IF (DATA & 1)   THEN DI17:= 1; ELSE DI17:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI18:= 1; ELSE DI18:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI19:= 1; ELSE DI19:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI20:= 1; ELSE DI20:= 0; ENDIF;
                       );

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLDEN GATE read digital inputs 21-40
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading digital inputs
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGDigital2 NAMED "Swegon GG DI2" TYPEID 21216 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
    DI21 : "Alarm no. 5"; 
    DI22 : "Alarm no. 6"; 
    DI23 : "Alarm no. 7"; 
    DI24 : "Alarm no. 8"; 
    DI25 : "Alarm no. 9"; 
    DI26 : "Alarm no. 10";
    DI27 : "Alarm no. 11";
    DI28 : "Alarm no. 12";
    DI29 : "Alarm no. 13";
    DI30 : "Alarm no. 14";
    DI31 : "Alarm no. 15";
    DI32 : "Alarm no. 16";
    DI33 : "Alarm no. 17";
    DI34 : "Alarm no. 18";
    DI35 : "Alarm no. 19";
    DI36 : "Alarm no. 20";
    DI37 : "Alarm no. 21";
    DI38 : "Alarm no. 22";
    DI39 : "Alarm no. 23";
    DI40 : "Alarm no. 24";

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalInput2 NAMED "DI 21-40" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(20);     % Start adress
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI21:= 1; ELSE DI21:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI22:= 1; ELSE DI22:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI23:= 1; ELSE DI23:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI24:= 1; ELSE DI24:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI25:= 1; ELSE DI25:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI26:= 1; ELSE DI26:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI27:= 1; ELSE DI27:= 0; ENDIF;
                       IF (DATA & 128) THEN DI28:= 1; ELSE DI28:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI29:= 1; ELSE DI29:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI30:= 1; ELSE DI30:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI31:= 1; ELSE DI31:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI32:= 1; ELSE DI32:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI33:= 1; ELSE DI33:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI34:= 1; ELSE DI34:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI35:= 1; ELSE DI35:= 0; ENDIF;
                       IF (DATA & 128) THEN DI36:= 1; ELSE DI36:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(IF (DATA & 1)   THEN DI37:= 1; ELSE DI37:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI38:= 1; ELSE DI38:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI39:= 1; ELSE DI39:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI40:= 1; ELSE DI40:= 0; ENDIF;
                       );

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLDEN GATE read digital inputs 41-60
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading digital inputs
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGDigital2 NAMED "Swegon GG DI3" TYPEID 21217 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
    DI41 : "Alarm no. 25"; 
    DI42 : "Alarm no. 26"; 
    DI43 : "Alarm no. 27"; 
    DI44 : "Alarm no. 28"; 
    DI45 : "Alarm no. 29"; 
    DI46 : "Alarm no. 30";
    DI47 : "Alarm no. 31";
    DI48 : "Alarm no. 32";
    DI49 : "Alarm no. 33";
    DI50 : "Alarm no. 34";
    DI51 : "Alarm no. 35";
    DI52 : "Alarm no. 36";
    DI53 : "Alarm no. 37";
    DI54 : "Alarm no. 38";
    DI55 : "Alarm no. 39";
    DI56 : "Alarm no. 40";
    DI57 : "Alarm no. 41";
    DI58 : "Alarm no. 42";
    DI59 : "Alarm no. 43";
    DI60 : "Alarm no. 44";

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalInput3 NAMED "DI 41-60" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(40);     % Start adress
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI41:= 1; ELSE DI41:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI42:= 1; ELSE DI42:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI43:= 1; ELSE DI43:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI44:= 1; ELSE DI44:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI45:= 1; ELSE DI45:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI46:= 1; ELSE DI46:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI47:= 1; ELSE DI47:= 0; ENDIF;
                       IF (DATA & 128) THEN DI48:= 1; ELSE DI48:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI49:= 1; ELSE DI49:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI50:= 1; ELSE DI50:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI51:= 1; ELSE DI51:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI52:= 1; ELSE DI52:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI53:= 1; ELSE DI53:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI54:= 1; ELSE DI54:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI55:= 1; ELSE DI55:= 0; ENDIF;
                       IF (DATA & 128) THEN DI56:= 1; ELSE DI56:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(IF (DATA & 1)   THEN DI57:= 1; ELSE DI57:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI58:= 1; ELSE DI58:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI59:= 1; ELSE DI59:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI60:= 1; ELSE DI60:= 0; ENDIF;
                       );

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SWEGON GOLDEN GATE read digital inputs 60
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading digital inputs
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-08 new script
%
DEVICETYPE SwegonGGDigital4 NAMED "Swegon GG DI4" TYPEID 21218 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
    DI61 : "Alarm no. 45"; 
    DI62 : "Alarm no. 46"; 
    DI63 : "Alarm no. 47"; 
    DI64 : "Alarm no. 48"; 
    DI65 : "Alarm no. 49"; 
    DI66 : "Alarm no. 50";
    DI67 : "Alarm no. 51";
    DI68 : "Alarm no. 52";
    DI69 : "Alarm no. 53";
    DI70 : "Alarm no. 54";
    DI71 : "Alarm no. 55";
    DI72 : "Alarm no. 56";
    DI73 : "Alarm no. 57";
    DI74 : "Alarm no. 58";
    DI75 : "Alarm no. 59";
    DI76 : "Alarm no. 60";
    DI77 : "Alarm no. 61";

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalInput4 NAMED "DI 60" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(60);     % Start adress
      DATA[4]  := RWORD(17);     % Number of inputs

    ANSWER SIZE 8
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI61:= 1; ELSE DI61:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI62:= 1; ELSE DI62:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI63:= 1; ELSE DI63:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI64:= 1; ELSE DI64:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI65:= 1; ELSE DI65:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI66:= 1; ELSE DI66:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI67:= 1; ELSE DI67:= 0; ENDIF;
                       IF (DATA & 128) THEN DI68:= 1; ELSE DI68:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI69:= 1; ELSE DI69:= 0; ENDIF;
                       IF (DATA & 2)   THEN DI70:= 1; ELSE DI70:= 0; ENDIF;
                       IF (DATA & 4)   THEN DI71:= 1; ELSE DI71:= 0; ENDIF;
                       IF (DATA & 8)   THEN DI72:= 1; ELSE DI72:= 0; ENDIF;
                       IF (DATA & 16)  THEN DI73:= 1; ELSE DI73:= 0; ENDIF;
                       IF (DATA & 32)  THEN DI74:= 1; ELSE DI74:= 0; ENDIF;
                       IF (DATA & 64)  THEN DI75:= 1; ELSE DI75:= 0; ENDIF;
                       IF (DATA & 128) THEN DI76:= 1; ELSE DI76:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(IF (DATA & 1)   THEN DI77:= 1; ELSE DI77:= 0; ENDIF;
                       );

    TIMEOUT 2000

  END;

END;