Skript kod
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
%
% Modified: 111213 OJ 2.2 changes
% Modified: 081203 PW Added TypeId 21164 - 68
%
% Device definition for PRODUAL wireless sensors version 2.2
% TEFL, TEUFL, KLUFL, LAFL, WPIR
%
% ABELKO AB Luleå
%
DEVICETYPE TEFL_V2_2 NAMED "Produal2.2_TEFL" TYPEID 22104 IS
PARAMETER
Id : "MasterID";
Nod : "NodID";
PUBLIC
V1 : "Temperatur 1" ["°C"]; % Node 1 TE? 248
V2 : "Temperatur 2" ["°C"]; % Noden 1 SP? 249
V3 : "Luftfuktighet" ["%RH"]; % Node 1 RH? 250
V4 : "Fläktstatus"; % Node 1 FAN? 251
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "TEFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register (var 31+4*Nod i 2.1)
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA / 10;);
DATA[7] -> RWORD(V3 := DATA / 10;);
DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "TEFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE TEUFL_V2_2 NAMED "Produal2.2TEUFL" TYPEID 22105 IS
PARAMETER
Id : "MasterID";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
V2 : "Spänning" ["V"];
%V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "TEUFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA / 10;);
%DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "TEUFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE KLUFL_V2_2 NAMED "Produal2.2KLUFL" TYPEID 22106 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
V2 : "Belysning" ["lx"];
V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "KLUFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA;);
DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "KLUFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE LAFL_V2_2 NAMED "Produal2.2_LAFL" TYPEID 22107 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
%V1 : "Temperatur 1" ["°C"];
V2 : "Belysmning" ["lx"];
%V3 : "Luftfuktighet" ["%RH"];
V4 : "Status";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "LAFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
%DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
% V1 := 0 - (1 + (65535-DATA))/10;
% ELSE
% V1 := DATA / 10;
% ENDIF;
% );
DATA[5] -> RWORD(V2 := DATA;);
%DATA[7] -> RWORD(V3 := DATA / 10;);
DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "LAFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE WPIR_V2_2 NAMED "Produal2.2_WPIR" TYPEID 22108 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
%V2 : "Temperatur 1" ["°C"];
V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "WPIR_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
%DATA[5] -> RWORD(V2 := DATA / 10;);
DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "WPIR_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
%
% Modified: 111213 OJ 2.2 changes
% Modified: 081203 PW Added TypeId 21164 - 68
%
% Device definition for PRODUAL wireless sensors version 2.2
% TEFL, TEUFL, KLUFL, LAFL, WPIR
%
% ABELKO AB Luleå
%
DEVICETYPE TEFL_V2_2 NAMED "Produal2.2_TEFL" TYPEID 22104 IS
PARAMETER
Id : "MasterID";
Nod : "NodID";
PUBLIC
V1 : "Temperatur 1" ["°C"]; % Node 1 TE? 248
V2 : "Temperatur 2" ["°C"]; % Noden 1 SP? 249
V3 : "Luftfuktighet" ["%RH"]; % Node 1 RH? 250
V4 : "Fläktstatus"; % Node 1 FAN? 251
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "TEFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register (var 31+4*Nod i 2.1)
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA / 10;);
DATA[7] -> RWORD(V3 := DATA / 10;);
DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "TEFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE TEUFL_V2_2 NAMED "Produal2.2TEUFL" TYPEID 22105 IS
PARAMETER
Id : "MasterID";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
V2 : "Spänning" ["V"];
%V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "TEUFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA / 10;);
%DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "TEUFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE KLUFL_V2_2 NAMED "Produal2.2KLUFL" TYPEID 22106 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
V2 : "Belysning" ["lx"];
V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "KLUFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
DATA[5] -> RWORD(V2 := DATA;);
DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "KLUFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE LAFL_V2_2 NAMED "Produal2.2_LAFL" TYPEID 22107 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
%V1 : "Temperatur 1" ["°C"];
V2 : "Belysmning" ["lx"];
%V3 : "Luftfuktighet" ["%RH"];
V4 : "Status";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "LAFL_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
%DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
% V1 := 0 - (1 + (65535-DATA))/10;
% ELSE
% V1 := DATA / 10;
% ENDIF;
% );
DATA[5] -> RWORD(V2 := DATA;);
%DATA[7] -> RWORD(V3 := DATA / 10;);
DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "LAFL_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;
DEVICETYPE WPIR_V2_2 NAMED "Produal2.2_WPIR" TYPEID 22108 IS
PARAMETER
Id : "MasterId";
Nod : "NodID";
PUBLIC
V1 : "Temperatur" ["°C"];
%V2 : "Temperatur 1" ["°C"];
V3 : "Luftfuktighet" ["%RH"];
%V4 : "Fläktstatus";
B1 : "Larm batteri";
B2 : "Avbrott kom.";
B3 : "PIR"; % Bara LAFL
B4 : "Tamper";
PRIVATE
Tmp;
BAUDRATE 38400;
CHECKSUM MODBUS SWAPPED;
TELEGRAM Read NAMED "WPIR_Read" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(04); % Modbus command "04h" read multiple inputregisters
DATA[2] := RWORD(247+4*(Nod-1)); % start register
DATA[4] := RWORD(4); % number of registers to read
ANSWER SIZE 13
DATA[0] = BYTE(Id);
DATA[1] = HEX(04);
DATA[3] -> RWORD(IF DATA > 32767 THEN % Negativ ?
V1 := 0 - (1 + (65535-DATA))/10;
ELSE
V1 := DATA / 10;
ENDIF;
);
%DATA[5] -> RWORD(V2 := DATA / 10;);
DATA[7] -> RWORD(V3 := DATA / 10;);
%DATA[9] -> RWORD(V4 := DATA;);
TIMEOUT 300
END;
TELEGRAM Larm NAMED "WPIR_Larm" IS
QUESTION
DATA[0] := BYTE(Id); % Modbus unit address
DATA[1] := HEX(02); % Modbus command "02h" read discrete inputs
DATA[2] <- RWORD(IF Nod>0 THEN
IF Tmp>2 THEN Tmp:=0; ELSE Tmp:=Tmp+1; ENDIF;
DATA := Tmp*100 + Nod - 1;
ELSE
DATA := Tmp*100;
ENDIF;
);
DATA[4] := RWORD(1); % number of bits to read
ANSWER SIZE 6
DATA[0] = BYTE(Id);
DATA[1] = HEX(02);
DATA[2] = BYTE(1);
DATA[3] -> BYTE(IF Tmp=0 THEN
IF (DATA & 1) THEN B1:=1; ELSE B1:=0; ENDIF;
ELSIF Tmp=1 THEN
IF (DATA & 1) THEN B2:=1; ELSE B2:=0; ENDIF;
ELSIF Tmp=2 THEN
IF (DATA & 1) THEN B3:=1; ELSE B3:=0; ENDIF;
ELSIF Tmp=3 THEN
IF (DATA & 1) THEN B4:=1; ELSE B4:=0; ENDIF;
ENDIF;
);
TIMEOUT 300
END;
END;