Siemens Saphir

Detaljer

Typ
Drivrutin
Upplaggd av
Ove Jansson, Abelko Innovation
Version
1
Uppdaterad
2013-08-27
Skapad
2013-08-27
Kategori
Modbus, Övrig utrustning
Visningar
4541

Beskrivning

Drivrutin till Siemens Saphir

Bruksanvisning

Siemens SAPHIR Modbus for ACX32 slave mode GEA COM4 Application v1.9-v2.x (pdf)
Siemens SAPHIR Modbus for ACX36 slave IV Produkt LB10 Application v1.2.x (pdf)
Siemens SAPHIR Modbus for ACX32 slave mode IV Produkt LB20 Application v3.x (pdf)

Juridisk information

Alla skript tillhandahålls i befintligt skick och all användning sker på eget ansvar. Felaktig använding kan leda till skadad eller förstörd utrustning.

Skript kod

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% 2010-02-02 Klara negativa värden på temperaturer
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Select device
%
% Skriptet gäller för: 
% - SAPHIR  S34 LB20  v3x (ACX32)
% - SAPHIR SS22 LB10 v12x (ACX36)
% - SAPHIR GEA COM4       (ACX32) 091117
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading selected values
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-01-07 initial version
% History: 2009-10-23 Added registers for ACX36
% History: 2009-11-17 Added registers for ACX32 GEA COM4 med inställningsmöjlighet
%

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Setpoint values
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Setpoint values
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirSetpoints NAMED "Saphir R1-18" TYPEID 21191 IS

  PARAMETER
    Id         : "Address";

  PUBLIC
                                      % Feedback for Holding reg
    R1   : "SetP Temp comf." ["°C"];  % Basic setpoint temp, Comfort   xx.y °C
    R2   : "SetP Temp econ." ["°C"];  % Basic setpoint temp, Economy   xx.y °C   (ACX32)
    R3   : "DeadZ Cool comf" ["°C"];  % Dead zone cooling, Comfort     xx.y °C
    R4   : "DeadZ Cool econ" ["°C"];  % Dead zone cooling, Economy     xx.y °C   (ACX32)
    R5   : "SetP Post-cond." ["°C"];  % Setpoint post-conditioning     xx.y °C   (ACX32)
   %R6
    R7   : "SetP Temp SMin"  ["°C"];  % Min setpoint SA temp, cascade  xx.y °C
    R8   : "SetP Temp SMax"  ["°C"];  % Max setpoint SA temp, cascade  xx.y °C
   %R9
   %R10  : "SetP Press SLow" ["Pa"];  % Setpoint pressure SA lowspeed  xxx Pa    (ACX32)
   %R11  : "SetP Press SHig" ["Pa"];  % Setpoint pressure SA highspeed xxx Pa    (ACX32)
   %R12  : "SetP Press ELow" ["Pa"];  % Setpoint pressure EA lowspeed  xxx Pa    (ACX32)
   %R13  : "SetP Press EHig" ["Pa"];  % Setpoint pressure EA highspeed xxx Pa    (ACX32)
    R10  : "SetP Flow SLow"  ["l/s"]; % Setpoint flow SA lowspeed      xxx l/s   (ACX32)
    R11  : "SetP Flow SHigh" ["l/s"]; % Setpoint flow SA highspeed     xxx l/s   (ACX32)
    R12  : "SetP Flow ELow"  ["l/s"]; % Setpoint flow EA lowspeed      xxx l/s   (ACX32)
    R13  : "SetP Flow EHigh" ["l/s"]; % Setpoint flow EA highspeed     xxx l/s   (ACX32)
    R14  : "SetP Flow"       ["l/s"]; % Setpoint flow                  xxx l/s   (GEA COM4)

   %R15  : "SetP Speed SLow" ["%"];   % Setpoint fixed SA lowspeed     xxx 0-100%
   %R16  : "SetP Speed SHig" ["%"];   % Setpoint fixed SA highspeed    xxx 0-100%
   %R17  : "SetP Speed ELow" ["%"];   % Setpoint fixed EA lowspeed     xxx 0-100%
   %R18  : "SetP Speed EHig" ["%"];   % Setpoint fixed EA highspeed    xxx 0-100%
    R15  : "SetP Press SLow" ["Pa"];  % Setpoint pressure SA lowspeed  xxx Pa    (ACX32)
    R16  : "SetP Press SHig" ["Pa"];  % Setpoint pressure SA highspeed xxx Pa    (ACX32)
    R17  : "SetP Press ELow" ["Pa"];  % Setpoint pressure EA lowspeed  xxx Pa    (ACX32)
    R18  : "SetP Press EHig" ["Pa"];  % Setpoint pressure EA highspeed xxx Pa    (ACX32)
    R19  : "SetP Pressure"   ["Pa"];  % Setpoint pressure              xxx Pa    (GEA COM4)


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Setpoints NAMED "Register 1-19" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(0);      % Start address register
      DATA[4]  := RWORD(19);     % Number of registers

    ANSWER SIZE 43
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(38);                  % Byte count
      DATA[3]  -> RWORD(R1   := DATA / 10;); % xx.y °C
      DATA[5]  -> RWORD(R2   := DATA / 10;); % xx.y °C
      DATA[7]  -> RWORD(R3   := DATA / 10;); % xx.y °C
      DATA[9]  -> RWORD(R4   := DATA / 10;); % xx.y °C
      DATA[11] -> RWORD(R5   := DATA / 10;); % xx.y °C
     %                  R6                   % No data
      DATA[15] -> RWORD(R7   := DATA / 10;); % xx.y °C
      DATA[17] -> RWORD(R8   := DATA / 10;); % xx.y °C
     %                  R9                   % No data
      DATA[21] -> RWORD(R10  := DATA;);      % xxx Pa / l/s
      DATA[23] -> RWORD(R11  := DATA;);      % xxx Pa / l/s
      DATA[25] -> RWORD(R12  := DATA;);      % xxx Pa / l/s
      DATA[27] -> RWORD(R13  := DATA;);      % xxx Pa / l/s
      DATA[29] -> RWORD(R14  := DATA;);      % xxx l/s                (GEA COM4)
      DATA[31] -> RWORD(R15  := DATA;);      % xxx Pa / 0-100%
      DATA[33] -> RWORD(R16  := DATA;);      % xxx Pa / 0-100%
      DATA[35] -> RWORD(R17  := DATA;);      % xxx Pa / 0-100%
      DATA[37] -> RWORD(R18  := DATA;);      % xxx Pa / 0-100%
      DATA[39] -> RWORD(R19  := DATA;);      % xxx Pa

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Analog values 1
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirAnalog1 NAMED "Saphir R20-33" TYPEID 21192 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

    R20 : "SetP Temp heat"  ["°C"];   % Actual heat setpoint temp control    xx.y °C
    R21 : "SetP Temp cool"  ["°C"];   % Actual cool setpoint temp control    xx.y °C
    R22 : "SetP Temp SHeat" ["°C"];   % Actual heat setpoint SA temp control xx.y °C
    R23 : "SetP Temp SCool" ["°C"];   % Actual cool setpoint SA temp control xx.y °C
    R24 : "SetP TempRemote" ["°C"];   % Presentation remote setpoint         xx.y °C
    R25 : "Temp Outdoor"    ["°C"];   % Outdoor temperature                  xx.y °C
    R26 : "Temp Supply air" ["°C"];   % SA temperature                       xx.y °C
    R27 : "Temp Frost"      ["°C"];   % Frost temperature                    xx.y °C
    R28 : "Temp Room"       ["°C"];   % Room/EA temperature                  xx.y °C
    R29 : "Temp Multi 2"    ["°C"];   % Multifunction temperature 2          xx.y °C
    R30 : "Temp Multi 1"    ["°C"];   % Multifunction temperature 1          xx.y °C
    R31 : "Flow SupplyAir"  ["l/s"];  % SA flow/pressure                     xxx l/s  (ACX32)
    R32 : "Flow ExhaustAir" ["l/s"];  % EA flow/pressure                     xxx l/s  (ACX32)
    R33 : "PressSupplyAir"  ["Pa"] ;  % SA pressure                          xxx Pa   (ACX32)
    R34 : "PressExhausAir"  ["Pa"] ;  % EA pressure                          xxx Pa   (GEA COM4)

    R39 : "Temp Room unit"  ["°C"];   % Room unit temperature                xx.y °C  (ACX36)

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Analog1 NAMED "Register 20-39" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(19);     % Start address register
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(40);                   % Byte count
      DATA[3]  -> RWORD(R20 := DATA / 10;);   % xx.y °C
      DATA[5]  -> RWORD(R21 := DATA / 10;);   % xx.y °C
      DATA[7]  -> RWORD(R22 := DATA / 10;);   % xx.y °C
      DATA[9]  -> RWORD(R23 := DATA / 10;);   % xx.y °C
      DATA[11] -> RWORD(R24 := DATA / 10;);   % xx.y °C

      DATA[13] -> RWORD(IF (DATA>=32768) THEN R25:=(DATA-65536)/10; ELSE R25:=DATA/10; ENDIF;);  % xx.y °C
      DATA[15] -> RWORD(IF (DATA>=32768) THEN R26:=(DATA-65536)/10; ELSE R26:=DATA/10; ENDIF;);  % xx.y °C
      DATA[17] -> RWORD(IF (DATA>=32768) THEN R27:=(DATA-65536)/10; ELSE R27:=DATA/10; ENDIF;);  % xx.y °C
      DATA[19] -> RWORD(IF (DATA>=32768) THEN R28:=(DATA-65536)/10; ELSE R28:=DATA/10; ENDIF;);  % xx.y °C
      DATA[21] -> RWORD(IF (DATA>=32768) THEN R29:=(DATA-65536)/10; ELSE R29:=DATA/10; ENDIF;);  % xx.y °C
      DATA[23] -> RWORD(IF (DATA>=32768) THEN R30:=(DATA-65536)/10; ELSE R30:=DATA/10; ENDIF;);  % xx.y °C

      DATA[25] -> RWORD(R31 := DATA;);        % xxx  l/s
      DATA[27] -> RWORD(R32 := DATA;);        % xxx  l/s
      DATA[29] -> RWORD(R33 := DATA;);        % xxx  Pa
      DATA[31] -> RWORD(R34 := DATA;);        % xxx  Pa       (GEA COM4)

      DATA[41] -> RWORD(R39 := DATA / 10;);   % xx.y °C       (ACX36)

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Analog values 2, Outputs, values and modes
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirAnalog2 NAMED "Saphir R40-51" TYPEID 21193 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

    R40 : "AO Heat"         ["%"];   % Analog out Heating               0-100%
    R41 : "AO Cool"         ["%"];   % Analog out Cooling               0-100%
    R42 : "AO HeatRecovery" ["%"];   % Analog out Heat recovery         0-100%
    R43 : "Efficiency HRC"  ["%"];   % Actual HRC efficiency            0-100%
    R44 : "Fan speed Sup."  ["%"];   % Frequency converter Supply fan   0-100%
    R45 : "Fan speed Exh."  ["%"];   % Frequency converter Exhaust fan  0-100%
    R46 : "Air Quality"     ["ppm"]; % Air quality                      0-2000 ppm  (ACX32)
    R47 : "AO Extra"        ["%"];   % Analog out Extra ctrl/sequence   0-100%      (ACX32)
   %R48 : "Not used"        [" "];   % Not used
   %R49 : "Not used"        [" "];   % Not used
    R50 : "Mode operation"       ;   % Actual operation mode ACX32      0-8
                                     % 0 = Damperkick  1 = Testtemp                 (ACX32)
                                     % 2 = Off         3 = Economy                  (ACX32)
                                     % 4 = Comfort     5 = Startup                  (ACX32)
                                     % 6 = Nightpurge  7 = Unoccupied               (ACX32)
                                     % 8 = Overrun                                  (ACX32)
                                     % Actual operation mode ACX32 GEA COM4   0-10
                                     % 0 = Off         1 = Timeschedule             (ACX32 GEA COM4)
                                     % 2 = LON Op      3 = Night Op                 (ACX32 GEA COM4)
                                     % 4 = Remote Op   5 = Timer Op                 (ACX32 GEA COM4)
                                     % 6 = Overrun     7 = Stopr                    (ACX32 GEA COM4)
                                     % 8 = Remote stop 9 = Test                     (ACX32 GEA COM4)
                                     % 10= Startup                                  (ACX32 GEA COM4)
                                     % Actual operation mode ACX36      0-8
                                     % 0 = Off         1 = Step 1                   (ACX36)
                                     % 2 = Step 2      3 = Undefined                (ACX36)
                                     % 4 = Testtemp    5 = Nightpurge               (ACX36)
                                     % 6 = Unoccupied  7 = Startup                  (ACX36)
                                     % 8 = Overrun     9 = Damper kick              (ACX36)
    R51 : "Mode fan";                % Actual fan mode ACX32            0-2
                                     % 0 = Off         1 = Lowspeed                 (ACX32)
                                     % 2 = Highspeed                                (ACX32)
                                     % Actual fan mode ACX32 GEA COM4   0-5
                                     % 0 = Internal TSP 1 = Off                     (ACX32 GEA COM4)
                                     % 2 = Eco Step 1   3 = Eco Step 2              (ACX32 GEA COM4
                                     % 4 = Comf Step 1  5 = Comf step 2             (ACX32 GEA COM4
                                     % Actual fan mode ACX36            0-2
                                     % 0 = Off         1 = Step 1                   (ACX36)
                                     % 2 = Step 2                                   (ACX36)

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Analog2 NAMED "Register 40-51" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(39);     % Start address register
      DATA[4]  := RWORD(12);     % Number of registers

    ANSWER SIZE 29
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(24);              % Byte count
      DATA[3]  -> RWORD(R40 := DATA;);   % 0-100%
      DATA[5]  -> RWORD(R41 := DATA;);   % 0-100%
      DATA[7]  -> RWORD(R42 := DATA;);   % 0-100%
      DATA[9]  -> RWORD(R43 := DATA;);   % 0-100%
      DATA[11] -> RWORD(R44 := DATA;);   % 0-100%
      DATA[13] -> RWORD(R45 := DATA;);   % 0-100%
      DATA[15] -> RWORD(R46 := DATA;);   % 0-2000 ppm
      DATA[17] -> RWORD(R47 := DATA;);   % 0-100%
     %                  R48              % No data
     %                  R49              % No data
      DATA[23] -> RWORD(R50 := DATA;);   % 0-8
      DATA[25] -> RWORD(R51 := DATA;);   % 0-2

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Digital alarms 1
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Digital alarms
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirAlarms1 NAMED "Saphir DI1-14" TYPEID 21194 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

   %DI1  : "Not used"       ;      % Not used
    DI2  : "Alarm A"        ;      % Alarm class A active
    DI3  : "Alarm B"        ;      % Alarm class B active
    DI4  : "Alarm C"        ;      % Alarm class C active
    DI5  : "Alarm TempDev"  ;      % Temperature deviation alarm
    DI6  : "Alarm Fire"     ;      % Fire alarm
    DI7  : "Alarm HRC"      ;      % HRC alarm
    DI8  : "Alarm PumpHeat" ;      % Heating pump alarm
    DI9  : "Alarm PumpCool" ;      % Cooling pump alarm
    DI10 : "Alarm AUX"      ;      % AUX alarm
    DI11 : "Alarm FanSupply";      % Supply fan alarm
    DI12 : "Alarm FanExhaus";      % Exhaust fan alarm
   %DI13 : "Not used"       ;      % Not used
    DI14 : "Alarm FrostProt";      % Frost protection alarm

   %DI6b : "Alarm Smoke"    ;      % Smoke alarm
   %DI8b : "Alarm Heating"  ;      % Heating alarm
   %DI9b : "Alarm Cooling"  ;      % Cooling alarm

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Alarms1 NAMED "Digital 1-14" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(0);      % Start adress
      DATA[4]  := RWORD(14);     % Number of inputs

    ANSWER SIZE 7
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(2);
      DATA[3]  -> BYTE(%IF (DATA & 1)   THEN DI1  := 1; ELSE DI1  := 0; ENDIF;
                        IF (DATA & 2)   THEN DI2  := 1; ELSE DI2  := 0; ENDIF;
                        IF (DATA & 4)   THEN DI3  := 1; ELSE DI3  := 0; ENDIF;
                        IF (DATA & 8)   THEN DI4  := 1; ELSE DI4  := 0; ENDIF;
                        IF (DATA & 16)  THEN DI5  := 1; ELSE DI5  := 0; ENDIF;
                        IF (DATA & 32)  THEN DI6  := 1; ELSE DI6  := 0; ENDIF;
                        IF (DATA & 64)  THEN DI7  := 1; ELSE DI7  := 0; ENDIF;
                        IF (DATA & 128) THEN DI8  := 1; ELSE DI8  := 0; ENDIF;

                       %IF (DATA & 32)  THEN DI6b := 1; ELSE DI6b := 0; ENDIF;
                       %IF (DATA & 128) THEN DI8b := 1; ELSE DI8b := 0; ENDIF;
                       );
      DATA[4]  -> BYTE( IF (DATA & 1)   THEN DI9  := 1; ELSE DI9  := 0; ENDIF;
                        IF (DATA & 2)   THEN DI10 := 1; ELSE DI10 := 0; ENDIF;
                        IF (DATA & 4)   THEN DI11 := 1; ELSE DI11 := 0; ENDIF;
                        IF (DATA & 8)   THEN DI12 := 1; ELSE DI12 := 0; ENDIF;
                       %IF (DATA & 16)  THEN DI13 := 1; ELSE DI13 := 0; ENDIF;
                        IF (DATA & 32)  THEN DI14 := 1; ELSE DI14 := 0; ENDIF;

                       %IF (DATA & 1)   THEN DI9b := 1; ELSE DI9b := 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;


%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Digital alarms 2
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Digital alarms
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirAlarms2 NAMED "Saphir DI15-28" TYPEID 21195 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

    DI15 : "Alarm HRC Frost";      % HRC frost alarm
    DI16 : "Alarm HRC Press";      % HRC pressure guard alarm         (ACX36)
    DI17 : "Alarm HRC Effic";      % HRC efficiency alarm
    DI18 : "Alarm UnitOverr";      % Unit override alarm
    DI19 : "Alarm Filter"   ;      % Filter alarm
    DI20 : "Alarm Room unit";      % Room unit alarm                  (ACX36)
    DI21 : "Alarm SensRoom" ;      % Room sensor alarm
    DI22 : "Alarm SensOutd" ;      % Out door sensor alarm
    DI23 : "Alarm SensSup." ;      % SA sensor alarm      1x0023
    DI24 : "Alarm SensFrost";      % Frost sensor alarm
    DI25 : "Alarm SensorM1" ;      % Multifunction sensor 1 alarm
    DI26 : "Alarm SensorM2" ;      % Multifunction sensor 2 alarm
    DI27 : "Alarm Runtime"  ;      % Runtime alarm
    DI28 : "Alarm DampSmoke";      % Smoke damper alarm

   %DI28 : "Alarm El.Heater";      % Electrical heater alarm          (GEA COM4)
   %DI29 : "Alarm Chiller"  ;      % Chiller alarm                    (GEA COM4)

   %DI21b : "Alarm SensExh.";      % Exhaust sensor alarm

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Alarms2 NAMED "Digital 15-28" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(14);     % Start adress
      DATA[4]  := RWORD(16);     % Number of inputs

    ANSWER SIZE 7
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(2);
      DATA[3]  -> BYTE( IF (DATA & 1)   THEN DI15 := 1; ELSE DI15 := 0; ENDIF;
                        IF (DATA & 2)   THEN DI16 := 1; ELSE DI16 := 0; ENDIF;  %(ACX36)
                        IF (DATA & 4)   THEN DI17 := 1; ELSE DI17 := 0; ENDIF;
                        IF (DATA & 8)   THEN DI18 := 1; ELSE DI18 := 0; ENDIF;
                        IF (DATA & 16)  THEN DI19 := 1; ELSE DI19 := 0; ENDIF;
                        IF (DATA & 32)  THEN DI20 := 1; ELSE DI20 := 0; ENDIF;  %(ACX36)
                        IF (DATA & 64)  THEN DI21 := 1; ELSE DI21 := 0; ENDIF;
                        IF (DATA & 128) THEN DI22 := 1; ELSE DI22 := 0; ENDIF;
                       %DI21b := DI21;
                       );
      DATA[4]  -> BYTE( IF (DATA & 1)   THEN DI23 := 1; ELSE DI23 := 0; ENDIF;
                        IF (DATA & 2)   THEN DI24 := 1; ELSE DI24 := 0; ENDIF;
                        IF (DATA & 4)   THEN DI25 := 1; ELSE DI25 := 0; ENDIF;
                        IF (DATA & 8)   THEN DI26 := 1; ELSE DI26 := 0; ENDIF;
                        IF (DATA & 16)  THEN DI27 := 1; ELSE DI27 := 0; ENDIF;
                        IF (DATA & 32)  THEN DI28 := 1; ELSE DI28 := 0; ENDIF;
                        IF (DATA & 32)  THEN DI28 := 1; ELSE DI28 := 0; ENDIF;
                       %IF (DATA & 64)  THEN DI29 := 1; ELSE DI29 := 0; ENDIF;  %(GEA COM4)
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Digital inputs 1
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Digital status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirDigital1 NAMED "Saphir DI33-45" TYPEID 21196 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

    DI33 : "DI Pump heat"      ;    % Heating pump
    DI34 : "DI Pump cool"      ;    % Cooling pump
    DI35 : "DI Damper Outd."   ;    % Out door damper
    DI36 : "DI alarm A"        ;    % Alarm class A output
    DI37 : "DI alarm B"        ;    % Alarm class B output
    DI38 : "DI Damper smoke"   ;    % Smoke damper
    DI39 : "DI CoolDX Step2"   ;    % Cooling DX Step 2
    DI40 : "DI FanSupp off"    ;    % Supply fan Off
    DI41 : "DI FanSupp st1"    ;    % Supply fan Step 1
    DI42 : "DI FanSupp st2"    ;    % Supply fan Step 2
    DI43 : "DI FanExhaustOff"  ;    % Exhaust fan Off
    DI44 : "DI FanExhaustStep1";    % Exhaust fan Step 1
    DI45 : "DI FanExhaustStep2";    % Exhaust fan Step 2

   %DI33b : "DI El. heat"      ;    % Electrical heater
   %DI34b : "DI DX step 1"     ;    % DX Step 1

   %DI39  : "DI Chiller ON"    ;    % Chiller in operation    (GEA COM4)

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Digital1 NAMED "Digital 33-45" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(32);     % Start address
      DATA[4]  := RWORD(13);     % Number of inputs

    ANSWER SIZE 7
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(2);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI33 := 1; ELSE DI33 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI34 := 1; ELSE DI34 := 0; ENDIF;
                       IF (DATA & 4)   THEN DI35 := 1; ELSE DI35 := 0; ENDIF;
                       IF (DATA & 8)   THEN DI36 := 1; ELSE DI36 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI37 := 1; ELSE DI37 := 0; ENDIF;
                       IF (DATA & 32)  THEN DI38 := 1; ELSE DI38 := 0; ENDIF;
                       IF (DATA & 64)  THEN DI39 := 1; ELSE DI39 := 0; ENDIF;
                       IF (DATA & 128) THEN DI40 := 1; ELSE DI40 := 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI41 := 1; ELSE DI41 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI42 := 1; ELSE DI42 := 0; ENDIF;
                       IF (DATA & 4)   THEN DI43 := 1; ELSE DI43 := 0; ENDIF;
                       IF (DATA & 8)   THEN DI44 := 1; ELSE DI44 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI45 := 1; ELSE DI45 := 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Digital inputs 2
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Digital status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2007-12-17 inital version
%
DEVICETYPE SaphirDigital2 NAMED "Saphir DI52-61" TYPEID 21197 IS

  PARAMETER
    Id         : "Address";

  PUBLIC

    DI52 : "Service Stop";      % Service switch Stop
    DI53 : "Service Step1";     % Service switch Step 1   (ACX32)
    DI54 : "Service Step2";     % Service switch Step 2   (ACX32)
    DI55 : "External Stop";     % External Stop           (ACX32)
    DI56 : "Control Stop";      % Control input Stop
    DI57 : "Control Step1";     % Control input Step 1
    DI58 : "Control Step2";     % Control input Step 2
    DI59 : "Control Room";      % Room control active
    DI60 : "Control Supply";    % Supply control active
    DI61 : "Control Exhaust";   % EA control active

    DI64 : "Emergency Stop";    % EA control active       (ACX36)

   %DI56b: "Timer in Stop";     % Timer input Stop
   %DI57b: "Timer in Step1" ;   % Timer input Step 1
   %DI58b: "Timer in Step2" ;   % Timer input Step 2

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Digital2 NAMED "Digital 52-61" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(51);     % Start address
      DATA[4]  := RWORD(16);     % Number of inputs

    ANSWER SIZE 7
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
      DATA[2]   = BYTE(2);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI52 := 1; ELSE DI52 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI53 := 1; ELSE DI53 := 0; ENDIF;
                       IF (DATA & 4)   THEN DI54 := 1; ELSE DI54 := 0; ENDIF;
                       IF (DATA & 8)   THEN DI55 := 1; ELSE DI55 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI56 := 1; ELSE DI56 := 0; ENDIF;
                       IF (DATA & 32)  THEN DI57 := 1; ELSE DI57 := 0; ENDIF;
                       IF (DATA & 64)  THEN DI58 := 1; ELSE DI58 := 0; ENDIF;
                       IF (DATA & 128) THEN DI59 := 1; ELSE DI59 := 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI60 := 1; ELSE DI60 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI61 := 1; ELSE DI61 := 0; ENDIF;
                      %IF (DATA & 4)   THEN DI62 := 1; ELSE DI62 := 0; ENDIF;
                      %IF (DATA & 8)   THEN DI63 := 1; ELSE DI63 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI64 := 1; ELSE DI64 := 0; ENDIF;   %(ACX36)
                      %IF (DATA & 32)  THEN DI65 := 1; ELSE DI65 := 0; ENDIF;
                      %IF (DATA & 64)  THEN DI66 := 1; ELSE DI66 := 0; ENDIF;
                      %IF (DATA & 128) THEN DI67 := 1; ELSE DI67 := 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for SIEMENS SAPHIR Analog settings
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2009-11-17 inital version
%
DEVICETYPE SaphirSettings NAMED "Saphir settings" TYPEID 21198 IS

  PARAMETER

   Id   : "Address";

    R1   : "SetP Temp comf." ["°C"];  % Basic setpoint temp, Comfort   xx.y °C
   %R2   : "SetP Temp econ." ["°C"];  % Basic setpoint temp, Economy   xx.y °C   (ACX32)
   %R3   : "DeadZ Cool comf" ["°C"];  % Dead zone cooling, Comfort     xx.y °C
   %R4   : "DeadZ Cool econ" ["°C"];  % Dead zone cooling, Economy     xx.y °C   (ACX32)
   %R5   : "SetP Post-cond." ["°C"];  % Setpoint post-conditioning     xx.y °C   (ACX32)
   %R6
   %R7   : "SetP Temp SMin"  ["°C"];  % Min setpoint SA temp, cascade  xx.y °C
   %R8   : "SetP Temp SMax"  ["°C"];  % Max setpoint SA temp, cascade  xx.y °C
   %R9

   %R10  : "SetP Press SLow" ["Pa"];  % Setpoint pressure SA lowspeed  xxx Pa    (ACX32)
   %R11  : "SetP Press SHig" ["Pa"];  % Setpoint pressure SA highspeed xxx Pa    (ACX32)
   %R12  : "SetP Press ELow" ["Pa"];  % Setpoint pressure EA lowspeed  xxx Pa    (ACX32)
   %R13  : "SetP Press EHig" ["Pa"];  % Setpoint pressure EA highspeed xxx Pa    (ACX32)

   %R10  : "SetP Flow SLow"  ["l/s"]; % Setpoint flow SA lowspeed      xxx l/s   (ACX32)
   %R11  : "SetP Flow SHigh" ["l/s"]; % Setpoint flow SA highspeed     xxx l/s   (ACX32)
   %R12  : "SetP Flow ELow"  ["l/s"]; % Setpoint flow EA lowspeed      xxx l/s   (ACX32)
   %R13  : "SetP Flow EHigh" ["l/s"]; % Setpoint flow EA highspeed     xxx l/s   (ACX32)

   %R14  : "SetP Flow"       ["l/s"]; % Setpoint flow                  xxx l/s   (GEA COM4)

   %R15  : "SetP Speed SLow" ["%"];   % Setpoint fixed SA lowspeed     xxx 0-100%
   %R16  : "SetP Speed SHig" ["%"];   % Setpoint fixed SA highspeed    xxx 0-100%
   %R17  : "SetP Speed ELow" ["%"];   % Setpoint fixed EA lowspeed     xxx 0-100%
   %R18  : "SetP Speed EHig" ["%"];   % Setpoint fixed EA highspeed    xxx 0-100%

   %R15  : "SetP Press SLow" ["Pa"];  % Setpoint pressure SA lowspeed  xxx Pa    (ACX32)
   %R16  : "SetP Press SHig" ["Pa"];  % Setpoint pressure SA highspeed xxx Pa    (ACX32)
   %R17  : "SetP Press ELow" ["Pa"];  % Setpoint pressure EA lowspeed  xxx Pa    (ACX32)
   %R18  : "SetP Press EHig" ["Pa"];  % Setpoint pressure EA highspeed xxx Pa    (ACX32)

   %R19  : "SetP Pressure"   ["Pa"];  % Setpoint pressure              xxx Pa    (GEA COM4)

    R50  : "BMS set mode";            % BMS override timeprogram mode 0-5        (LBA10/20)
                                      % 0 = Internal TSP 1 = Off
                                      % 2 = Eco Step 1   3 = Eco Step 2
                                      % 4 = Comf Step 1  5 = Comf step 2

   %R51  : "BMS set mode";            % BMS override timeprogram mode 0-5        (GEA)
                                      % 0 = Internal TSP 1 = Off
                                      % 2 = Eco Step 1   3 = Eco Step 2
                                      % 4 = Comf Step 1  5 = Comf step 2
    
  PUBLIC

  PRIVATE
   Cnt;

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Settings1 NAMED "Setvalues" IS

    QUESTION
      DATA[0]  := BYTE(Id);
      DATA[1]  := HEX(06);   %Write singel register
      DATA[2]  <- RWORD(     %Start adress (regnr-1)
        Cnt := Cnt + 1;
        IF Cnt>1 THEN Cnt:=0;
        ENDIF;

        IF    Cnt=0 THEN DATA := 0;        %R1
        ELSIF Cnt=1 THEN DATA := 49;       %R50
       %ELSIF Cnt=2 THEN DATA := 2;        %R3
       %ELSIF Cnt=3 THEN DATA := 3         %R4
       %ELSIF Cnt=4 THEN DATA := 4;        %R5
        ENDIF;

      );

      DATA[4]  <- RWORD(

        IF Cnt=0 THEN
          IF    R1<0   THEN DATA := 0;          %Basic setpoint temp, Comfort
          ELSIF R1>30  THEN DATA := 300;
          ELSE              DATA := R1*10;
          ENDIF;
        ELSIF Cnt=1  THEN
          IF    R50<0  THEN DATA := 0;          %BMS override timeprogram 0-5
          ELSIF R50>5  THEN DATA := 0;
          ELSE              DATA := R50;
          ENDIF;
        %ELSIF Cnt=2 THEN
        %  IF    SR150<0     THEN DATA := 0;         %SR150 SupTempMinSet 0-18.00 °C
        %  ELSIF SR150>18.00 THEN DATA := 1800;
        %  ELSE                   DATA := SR150*100;
        %  ENDIF;
        %ELSIF Cnt=3 THEN
        %  IF    SR151<20.00 THEN DATA := 2000;      %SR151 SupTempMaxSet 20.00-50.00 °C
        %  ELSIF SR151>50.00 THEN DATA := 5000;
        %  ELSE                   DATA := SR151*100;
        %  ENDIF;
        %ELSIF Cnt=4 THEN
        %  IF    SR152< 1.00 THEN DATA := 100;       %SR152 SupTempDiffSet 1.00-15.00 °C
        %  ELSIF SR152>15.00 THEN DATA := 1500;
        %  ELSE                   DATA := SR152*100;
        %  ENDIF;
        ENDIF;

      );

    ANSWER SIZE 8
      DATA[0] = BYTE(Id);
      DATA[1] = HEX(06);

    TIMEOUT 1000

  END;

END;

Användarnas noteringar

Du måste vara inloggad för att göra en notering. Bli medlem eller logga in. Vi använder en moderator som godkänner noteringarna innan de visas.