Regin EXO Compact

Detaljer

Typ
Drivrutin
Upplaggd av
Ove Jansson, Abelko Innovation
Version
1
Uppdaterad
2013-08-27
Skapad
2013-08-27
Kategori
Modbus, Övrig utrustning
Visningar
2808

Beskrivning

Drivrutin till Regin EXO Compact

Bruksanvisning

EXOcompact Manual (pdf)

Juridisk information

Alla skript tillhandahålls i befintligt skick och all användning sker på eget ansvar. Felaktig använding kan leda till skadad eller förstörd utrustning.

Skript kod

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for REGIN EXO Compact Analog inputs/outputs
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU

% Author:  Peter Widetun, ABELKO AB Luleå 
% History: 2008-10-23 initial version
%
DEVICETYPE ReginAnalog NAMED "Regin analog" TYPEID 21260 IS 
  
  PARAMETER
    Id         : "Adress";
   
  PUBLIC
    V1       : "AI_GT2_1_Rum" ["°C"];
    V2       : "AI_GT2_2_Rum" ["°C"];
    V3       : "AI_GTU_Ute"   ["°C"];
    V4       : "AI_GT8"       ["°C"];
    V5       : "AI_GT1_1"     ["°C"];
    V6       : "AI_GT1_2"     ["°C"];
    V7       : "AI_GP1"       ["Pa"];
    V8       : "AI_GP2"       ["Pa"];
    V9       : "AU_TF1"       ["%"]; 
    V10      : "AU_FF1"       ["%"]; 
    V11      : "AU_VVX"       ["%"]; 
    V12      : "AU_SV1"       ["%"]; 

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;
  
  TELEGRAM AnalogInput NAMED "Läs analog" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(0);      % Start address register
      DATA[4]  := RWORD(12);     % Number of registers

    ANSWER SIZE 29
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(24);      % Byte count
      DATA[3]  -> RWORD(IF (DATA>=32768) THEN V1:=(DATA-65536)/10; ELSE V1:=DATA/10; ENDIF;);  % 10*
      DATA[5]  -> RWORD(IF (DATA>=32768) THEN V2:=(DATA-65536)/10; ELSE V2:=DATA/10; ENDIF;);  % 10*
      DATA[7]  -> RWORD(IF (DATA>=32768) THEN V3:=(DATA-65536)/10; ELSE V3:=DATA/10; ENDIF;);  % 10*
      DATA[9]  -> RWORD(IF (DATA>=32768) THEN V4:=(DATA-65536)/10; ELSE V4:=DATA/10; ENDIF;);  % 10*
      DATA[11] -> RWORD(IF (DATA>=32768) THEN V5:=(DATA-65536)/10; ELSE V5:=DATA/10; ENDIF;);  % 10*
      DATA[13] -> RWORD(IF (DATA>=32768) THEN V6:=(DATA-65536)/10; ELSE V6:=DATA/10; ENDIF;);  % 10*
      DATA[15] -> RWORD(V7 := DATA / 10;);
      DATA[17] -> RWORD(V8 := DATA / 10;);
      DATA[19] -> RWORD(V9 := DATA / 10;);
      DATA[21] -> RWORD(V10:= DATA / 10;);
      DATA[23] -> RWORD(V11:= DATA / 10;);
      DATA[25] -> RWORD(V12:= DATA / 10;);

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for REGIN EXO Compact settings
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU

% Author:  Peter Widetun, ABELKO AB Luleå 
% History: 2008-10-23 initial version
%
DEVICETYPE ReginOutput NAMED "Regin ställ" TYPEID 21261 IS 
  
  PARAMETER
    Id     :"Adress";
    
    S1     :"Börvärde Reg1"["°C"];
    S2     :"Börvärde Reg2"["°C"];
    S3     :"Larmåterställ";

  PUBLIC
    V1     :"Börvärde Reg1"["°C"];
    V2     :"Börvärde Reg2"["°C"];
   %V1     :"Läst BV Reg1"["°C"];
   %V2     :"Läst BV Reg2"["°C"];

  PRIVATE

  BAUDRATE 9600;
  CHECKSUM MODBUS SWAPPED;
  
  TELEGRAM WriteSet NAMED "Ställ värden" IS

    QUESTION
      DATA[0] := BYTE(Id);    % Modbus unit address
      DATA[1] := HEX(10);     % Modbus command "0x10" write multiple registers
      DATA[2] := RWORD(0);    % start register
      DATA[4] := RWORD(3);    % number of registers to write
      DATA[6] := BYTE(6);     % number of bytes
      DATA[7] <- RWORD(DATA := S1*10;
                       V1   := S1;
                       );
      DATA[9] <- RWORD(DATA := S2*10;
                       V2   := S2;
                       );
      DATA[11]<- RWORD(DATA :=(S3>0););

    ANSWER SIZE 8
      DATA[0] = BYTE(Id);
      DATA[1] = HEX(10);
     %DATA[2] = RWORD(0);     % start register
     %DATA[4] = RWORD(3);     % number of registers to write

    TIMEOUT 2000

  END;

%  TELEGRAM ReadSet NAMED "Läs värden" IS
%  
%      QUESTION
%      DATA[0]  := BYTE(Id);      % Modbus unit address
%      DATA[1]  := HEX(03);       % Modbus command "3h" Read holding registers
%      DATA[2]  := RWORD(0);      % Start address register
%      DATA[4]  := RWORD(2);      % Number of registers
%
%    ANSWER SIZE 9
%      DATA[0]   = BYTE(Id);      % ID
%      DATA[1]   = HEX(03);       % Modbus command "03h" Read holding registers
%      DATA[2]   = BYTE(4);       % Byte count
%      DATA[3]  -> RWORD(V1 := DATA / 10;);
%      DATA[5]  -> RWORD(V2 := DATA / 10;);
%
%    TIMEOUT 2000
%
%  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for REGIN EXO Compact Digital inputs/outputs
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU

% Author:  Peter Widetun, ABELKO AB Luleå 
% History: 2008-10-23 initial version
%
DEVICETYPE ReginDigital NAMED "Regin DI/DU" TYPEID 21262 IS 
  
  PARAMETER
    Id         : "Adress";
   
  PUBLIC

    DI1        : "DU_TF1";
    DI2        : "DU_FF1";
    DI3        : "DI_P1";
    DI4        : "DI_TM1";
    DI5        : "DI_TM2";
    DI6        : "DU_BSX_3";
    DI7        : "DU_SUMMALARM_A";
    DI8        : "DU_SUMMALARM_B";
    DI9        : "DU_BSX_1_2";
                                  
  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;
  
  TELEGRAM DigitalInput NAMED "Digital status" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(0);      % Start adress
      DATA[4]  := RWORD(9);      % Number of inputs
      
    ANSWER SIZE 7
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02); 
      DATA[2]   = BYTE(2);
      DATA[3]  -> BYTE(IF (DATA & 1)   THEN DI1 := 1; ELSE DI1 := 0; ENDIF;
                       IF (DATA & 2)   THEN DI2 := 1; ELSE DI2 := 0; ENDIF;
                       IF (DATA & 4)   THEN DI3 := 1; ELSE DI3 := 0; ENDIF;
                       IF (DATA & 8)   THEN DI4 := 1; ELSE DI4 := 0; ENDIF;
                       IF (DATA & 16)  THEN DI5 := 1; ELSE DI5 := 0; ENDIF;
                       IF (DATA & 32)  THEN DI6 := 1; ELSE DI6 := 0; ENDIF;
                       IF (DATA & 64)  THEN DI7 := 1; ELSE DI7 := 0; ENDIF;
                       IF (DATA & 128) THEN DI8 := 1; ELSE DI8 := 0; ENDIF;
                       );
      DATA[4]  -> BYTE(IF (DATA & 1)   THEN DI9 := 1; ELSE DI9 := 0; ENDIF;
                       );

    TIMEOUT 2000

  END;

END;