% Device definition for CARRIER read input registers 0x4100-0x4113
% (Modbus channel 0-19 with one decimal)
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-04 initial version
%
DEVICETYPE CarrierAnalogA NAMED "Carrier analogA" TYPEID 21250 IS

  PARAMETER
    Id  : "Address";

  PUBLIC
                                      % Modbus channel             Point name  Register
    R1  : "A Hotgas t mean"  ["°C"];  % 0  Hetgas temp. Average    dt_a        0x4100 (16640)
    R2  : "A Hotgas t kpr1"  ["°C"];  % 1  Hetgas temp. kompr A1   CPA1_DGT    0x4101
    R3  : "A Hotgas t kpr2"  ["°C"];  % 2  Hetgas temp. kompr A2   CPA2_DGT    0x4102
    R4  : "A Suction gas t"  ["°C"];  % 3  Suggas temp             SST_A       0x4103
    R5  : "A Fluid t ext."   ["°C"];  % 4  Vätske temp. (extern)               0x4104
    R6  : "A KB temp in"     ["°C"];  % 5  KB temp. in             COOL_EWT    0x4105
    R7  : "A KB temp out"    ["°C"];  % 6  KB temp. ut             COOL_LWT    0x4106
    R8  : "A KM temp in"     ["°C"];  % 7  KM temp. in             COND_EWT    0x4107
    R9  : "A KM temp out"    ["°C"];  % 8  KM temp. ut             COND_LWT    0x4108
    R10 : "A Hotgas press"   ["Pa"];  % 9  Hetgas tryck            DP_A        0x4109
    R11 : "A Suction press"  ["Pa"];  % 10 Sug tryck               SP_A        0x410A
    R12 : "A Power ext."     ["W"];   % 11 Eleffekt (extern)                   0x410B
    R13 : "A Cooling kpr1"   [" "];   % 12 Motorkylning kompr A1   cpa1_mc1    0x410C
    R14 : "A Cooling kpr2"   [" "];   % 13 Motorkylning kompr A2   cpa2_mc1    0x410D
    R15 : "A Motor t kpr1"   ["°C"];  % 14 Motor temp.  kompr A1   CPA1_TMP    0x410E
    R16 : "A Motor t kpr2"   ["°C"];  % 15 Motor temp.  kompr A2   CPA2_TMP    0x410F
    R17 : "A R17"            [" "];   % 16                                     0x4110
    R18 : "A R18"            [" "];   % 17                                     0x4111
    R19 : "A R19"            [" "];   % 18                                     0x4112
    R20 : "A R20"            [" "];   % 19                                     0x4113

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInputA NAMED "Circuit A" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(16640);  % Start address register (0x4100)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(R1  := DATA/10;);
      DATA[5]  -> RWORD(R2  := DATA/10;);
      DATA[7]  -> RWORD(R3  := DATA/10;);
      DATA[9]  -> RWORD(R4  := DATA/10;);
      DATA[11] -> RWORD(R5  := DATA/10;);
     %DATA[13] -> RWORD(R6  := DATA/10;);
      DATA[13] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R6 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R6 := DATA / 1000;
                        ENDIF;
                        );
     %DATA[15] -> RWORD(R7  := DATA/10;);
      DATA[15] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R7 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R7 := DATA / 1000;
                        ENDIF;
                        );
      DATA[17] -> RWORD(R8  := DATA/10;);
      DATA[19] -> RWORD(R9  := DATA/10;);
      DATA[21] -> RWORD(R10 := DATA/10;);
      DATA[23] -> RWORD(R11 := DATA/10;);
      DATA[25] -> RWORD(R12 := DATA/10;);
      DATA[27] -> RWORD(R13 := DATA/10;);
      DATA[29] -> RWORD(R14 := DATA/10;);
      DATA[31] -> RWORD(R15 := DATA/10;);
      DATA[33] -> RWORD(R16 := DATA/10;);
      DATA[35] -> RWORD(R17 := DATA/10;);
      DATA[37] -> RWORD(R18 := DATA/10;);
      DATA[39] -> RWORD(R19 := DATA/10;);
      DATA[41] -> RWORD(R20 := DATA/10;);

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for CARRIER read input registers 0x4114-0x4127
% (Modbus channel 20-39 with one decimal)
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-04 initial version
%
DEVICETYPE CarrierAnalogB NAMED "Carrier analogB" TYPEID 21251 IS

  PARAMETER
    Id  : "Address";

  PUBLIC
                                      % Modbus channel             Point name  Register
    R21 : "B Hotgas t mean"  ["°C"];  % 20 Hetgas temp. Average    dt_b       0x4114 (16660)
    R22 : "B Hotgas t kpr1"  ["°C"];  % 21 Hetgas temp. kompr B1   CPB1_DGT   0x4115
    R23 : "B Hotgas t kpr2"  ["°C"];  % 22 Hetgas temp. kompr B2   CPB2_DGT   0x4116
    R24 : "B Suction gas t"  ["°C"];  % 23 Suggas temp             SST_B      0x4117
    R25 : "B Fluid t ext."   ["°C"];  % 24 Vätske temp. (extern)              0x4118
    R26 : "B KB temp in"     ["°C"];  % 25 KB temp. in             COOL_EWT   0x4119
    R27 : "B KB temp out"    ["°C"];  % 26 KB temp. ut             COOL_LWT   0x411A
    R28 : "B KM temp in"     ["°C"];  % 27 KM temp. in             COND_EWT   0x411B
    R29 : "B KM temp out"    ["°C"];  % 28 KM temp. ut             COND_LWT   0x411C
    R30 : "B Hotgas press"   ["Pa"];  % 29 Hetgas tryck            DP_B       0x411D
    R31 : "B Suction press"  ["Pa"];  % 30 Sug tryck               SP_B       0x411E
    R32 : "B Power ext."     ["W"];   % 31 Eleffekt     (extern)              0x411F
    R33 : "B Cooling kpr1"   [" "];   % 32 Motorkylning kompr B1   cpb1_mc1   0x4120
    R34 : "B Cooling kpr2"   [" "];   % 33 Motorkylning kompr B2   cpb2_mc1   0x4121
    R35 : "B Motor t kpr1"   ["°C"];  % 34 Motor temp.  kompr B1   CPB1_TMP   0x4122
    R36 : "B Motor t kpr2"   ["°C"];  % 35 Motor temp.  kompr B2   CPB2_TMP   0x4123
    R37 : "B R37"            [" "];   % 36                                    0x4124
    R38 : "B R38"            [" "];   % 37                                    0x4125
    R39 : "B R39"            [" "];   % 38                                    0x4126
    R40 : "B R40"            [" "];   % 39                                    0x4127

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInputB NAMED "Circuit B" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(16660);  % Start address register (0x4114)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
      DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(R21 := DATA/10;);
      DATA[5]  -> RWORD(R22 := DATA/10;);
      DATA[7]  -> RWORD(R23 := DATA/10;);
      DATA[9]  -> RWORD(R24 := DATA/10;);
      DATA[11] -> RWORD(R25 := DATA/10;);
     %DATA[13] -> RWORD(R26 := DATA/10;);
      DATA[13] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R26 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R26 := DATA / 1000;
                        ENDIF;
                        );
     %DATA[15] -> RWORD(R27 := DATA/10;);
      DATA[15] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R27 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R27 := DATA / 1000;
                        ENDIF;
                        );
      DATA[17] -> RWORD(R28 := DATA/10;);
      DATA[19] -> RWORD(R29 := DATA/10;);
      DATA[21] -> RWORD(R30 := DATA/10;);
      DATA[23] -> RWORD(R31 := DATA/10;);
      DATA[25] -> RWORD(R32 := DATA/10;);
      DATA[27] -> RWORD(R33 := DATA/10;);
      DATA[29] -> RWORD(R34 := DATA/10;);
      DATA[31] -> RWORD(R35 := DATA/10;);
      DATA[33] -> RWORD(R36 := DATA/10;);
      DATA[35] -> RWORD(R37 := DATA/10;);
      DATA[37] -> RWORD(R38 := DATA/10;);
      DATA[39] -> RWORD(R39 := DATA/10;);
      DATA[41] -> RWORD(R40 := DATA/10;);

    TIMEOUT 2000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for CARRIER read input registers 0x4128-0x413B
% (Modbus channel 40-59 with one decimal)
%
% Settings module:
%       Parity: None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2008-08-04 initial version
%
DEVICETYPE CarrierAnalogC NAMED "Carrier analogC" TYPEID 21252 IS

  PARAMETER
    Id  : "Address";

  PUBLIC
                                      % Modbus channel             Point name  Register
    R41 : "C Hotgas t mean"  ["°C"];  % 40 Hetgas temp. Average    dt_c        0x4128 (16680)
    R42 : "C Hotgas t kpr1"  ["°C"];  % 41 Hetgas temp. kompr C1   CPC1_DGT    0x4129
    R43 : "C Hotgas t kpr2"  ["°C"];  % 42 Hetgas temp. kompr C2   CPC2_DGT    0x412A
    R44 : "C Suction gas t"  ["°C"];  % 43 Suggas temp             SST_C       0x412B
    R45 : "C Fluid t ext."   ["°C"];  % 44 Vätske temp. (extern)               0x412C
    R46 : "C KB temp in"     ["°C"];  % 45 KB temp. in             COOL_EWT    0x412D
    R47 : "C KB temp out"    ["°C"];  % 46 KB temp. ut             COOL_LWT    0x412E
    R48 : "C KM temp in"     ["°C"];  % 47 KM temp. in             COND_EWT    0x412F
    R49 : "C KM temp out"    ["°C"];  % 48 KM temp. ut             COND_LWT    0x4130
    R50 : "C Hotgas press"   ["Pa"];  % 49 Hetgas tryck            DP_C        0x4131
    R51 : "C Suction press"  ["Pa"];  % 50 Sug    tryck            SP_C        0x4132
    R52 : "C Power ext."     ["W"];   % 51 Eleffekt (extern)                   0x4133
    R53 : "C Cooling kpr1"   [" "];   % 52 Motorkylning kompr C1   cpc1_mc1    0x4134
    R54 : "C Cooling kpr2"   [" "];   % 53 Motorkylning kompr C2   cpc2_mc1    0x4135
    R55 : "C Motor t kpr1"   ["°C"];  % 54 Motor temp.  kompr C1   CPC1_TMP    0x4136
    R56 : "C Motor t kpr2"   ["°C"];  % 55 Motor temp.  kompr C2   CPC2_TMP    0x4137
    R57 : "C R57"            [" "];   % 56                                     0x4138
    R58 : "C R58"            [" "];   % 57                                     0x4139
    R59 : "C R59"            [" "];   % 58                                     0x413A
    R60 : "C R60"            [" "];   % 59                                     0x413B

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInputC NAMED "Circuit C" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(16680);  % Start address register (0x4128)
     %DATA[4]  := RWORD(20);     % Number of registers
      DATA[4]  := RWORD(19);     % Number of registers

   %ANSWER SIZE 45
    ANSWER SIZE 43
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[2]   = BYTE(38);      % Byte count
      DATA[3]  -> RWORD(R41 := DATA/10;);
      DATA[5]  -> RWORD(R42 := DATA/10;);
      DATA[7]  -> RWORD(R43 := DATA/10;);
      DATA[9]  -> RWORD(R44 := DATA/10;);
      DATA[11] -> RWORD(R45 := DATA/10;);
     %DATA[13] -> RWORD(R46 := DATA/10;);
      DATA[13] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R46 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R46 := DATA / 1000;
                        ENDIF;
                        );
     %DATA[15] -> RWORD(R47 := DATA/10;);
      DATA[15] -> RWORD(IF DATA > 32767 THEN     % Negativ ?
                          R47 := 0 - (1 + (65535-DATA)) / 1000;
                        ELSE
                          R47 := DATA / 1000;
                        ENDIF;
                        );
      DATA[17] -> RWORD(R48 := DATA/10;);
      DATA[19] -> RWORD(R49 := DATA/10;);
      DATA[21] -> RWORD(R50 := DATA/10;);
      DATA[23] -> RWORD(R51 := DATA/10;);
      DATA[25] -> RWORD(R52 := DATA/10;);
      DATA[27] -> RWORD(R53 := DATA/10;);
      DATA[29] -> RWORD(R54 := DATA/10;);
      DATA[31] -> RWORD(R55 := DATA/10;);
      DATA[33] -> RWORD(R56 := DATA/10;);
      DATA[35] -> RWORD(R57 := DATA/10;);
      DATA[37] -> RWORD(R58 := DATA/10;);
      DATA[39] -> RWORD(R59 := DATA/10;);
     %DATA[41] -> RWORD(R60 := DATA/10;);

    TIMEOUT 2000

  END;